About Fabricated Data Center Fanwall AI All-in-room

The pre-integrated indoor computing power center infrastructure solution integrates functions such as power supply and  distribution, chilled water air walls and pipelines, CDU and secondary pipelines, manifolds, cabinets, and environmental  monitoring. It supports AI equipment by providing a stable, reliable, and energy-efficient infrastructure environment.

Product Introduction
Intelligence
Sustainability
Rapid Deployment
Intelligent operation and maintenance, reducing costs and improving resource utilization
Utilizes liquid cooling with cold plates, supplemented by air cooling, achieving an air-to-liquid ratio of 1/9 and low PUE for modules Employs chilled water air wall cooling, compatible with air cooling servers
Flat layout, skid-mounted segmented transport and positioning, multi-story buildings, on-site assembly of components Supports flexible deployment and quick expansion
Specification
FDC-FW-AI-AIR
Altitude range ≤1000 meters
Ambient temperature 18~35℃
Ambient humidity 5%-95%RH
Module external dimensions Total module dimensions: 7400mm L * 3100mm W * 2550mm H, transportable in sections, standard shipping container transport
Closed aisle Closed hot aisle, width 1500mm, flip skylight
Aisle door Double doors on both sides of the aisle
Raised floor Height 550mm
Cabinet power density 40KW/cabinet, expandable to 80KW/cabinet
Cabinet dimensions Standard 19" cabinet (600mm x 1200mm x 2000mm), 42U
Cabinet usable height (U) 336
Number of cabinets 8
Cabinet front and rear doors Front door single-opening mesh, no rear door
Power distribution cabinet 2-way UPS independent power supply for IT cabinets, air wall ATS switchover power supply, 380V/415V/50Hz
Power distribution capacity UPS 2*800A
PDU A/B dual circuit, 40A/3P
Modular UPS None
Backup time None
Cooling method Liquid cooling (cold plate) + air cooling (chilled water air wall)
Load air/liquid ratio Air/liquid ratio: 10%/90%~30%/70%