Prefabricated outdoor integrated computing center infrastructure solution, integrating functions such as power supply and distribution, integrated cooling source, air-cooled row-based air conditioning, cabinets, environmental monitoring, fire protection, and lightning protection, providing a stable, reliable, and energy-efficient infrastructure environment for AI equipment.
| Altitude range | ≤1000 meters |
| Ambient temperature | -15~55℃, if the ambient temperature is ≤-15℃ or ≥55℃, AC and integrated cold source need to be customized separately. |
| Ambient humidity | 5%-95%RH |
| External dimensions | 13716mm L * 2438mm W * 2896mm H, 45 foot standard container size, with classification society certification, meeting maritime and land transportation standards. |
| Protection level | IP55 |
| Cabinet power density | 40KW/cabinet |
| Cabinet dimensions | Standard 19" cabinet (600mm x 1200mm x 2000mm), 42U |
| Cabinet usable height (U) | 336 |
| Number of cabinets(units) | 8 |
| Cabinet front and rear doors | None |
| Enclosed aisle | Hot and cold aisle isolation |
| Row header cabinet | 2-way mains power input via ATS switching + 2-way U-power independent supply, 380V/415V/50Hz |
| Power distribution capacity | Mains power 2*630A/U-power 2*630A |
| PDU | A/B dual circuit, 40A/3P |
| Modular UPS | None |
| Backup power supply time | None |
| Cooling method | Liquid cooling (cold plate) + air cooling (row-based air conditioning) |
| Load air/liquid ratio | Liquid: 70% Air: 30% |